Skip to content

PV Glossary

All technical terms for photovoltaics, MPPT design, cable sizing and mounting structure at a glance. Click a term for the detailed explanation.

68 terms

Module electrics(11)

Voc — Open Circuit Voltage

Module voltage with no load. Most important value for string design because Voc rises at low temperatures.

Detail

Voc (open-circuit voltage) is the highest voltage a PV module delivers when no current flows. At -10 °C it can be 10-12 % above the STC value. The maximum input voltage of the MPPT must be rated for this, otherwise the charge controller is damaged. Rule of thumb: (module Voc × number in series) × 1.12 ≤ MPPT vocMax.

See also: Vmpp, Voc Temperature Coefficient

Vmpp — MPP Voltage

Voltage at the optimal operating point (Maximum Power Point). Typically 80-85% of Voc.

Detail

Vmpp is the voltage at which the module delivers its maximum power. The MPPT charge controller actively regulates to this point. Important: the sum of the Vmpp of all modules in series must lie within the MPPT operating window, otherwise the tracker cannot hold the point.

See also: Voc, MPP

Isc — Short Circuit Current

Maximum current with shorted terminals. Used for fuse sizing.

Detail

Isc (short-circuit current) is the current that flows when the module terminals are connected directly. For cable and fuse sizing one typically calculates with Isc × 1.25, to keep a reserve for high irradiance (>1000 W/m²).

See also: Imp

Imp — MPP Current

Current at the optimal operating point. Typically 92-95% of Isc.

Detail

Imp is the current the module delivers at the MPP. Imp × Vmpp gives the maximum power (Pmpp = power in Wp). When sizing the MPPT, the tracker current limit (ipvMaxA) is compared with the Imp per string.

See also: Isc, MPP

Power in Wp / kWp

Watt-peak is the rated power under STC. A 10 kWp system has e.g. 23 modules at 435 Wp.

Detail

Wp (watt-peak) is the module power under standard test conditions (STC: 1000 W/m², 25 °C cell temperature, AM 1.5). In real operation the power is usually 10-20 % below Wp because of higher module temperature, soiling and losses. 1 kWp = 1000 Wp.

See also: STC, MPP

STC — Standard Test Conditions

Standardized measurement: 1000 W/m², 25 °C cell, AM 1.5.

Detail

Standard test conditions are the standardised conditions under which Voc, Vmpp, Isc, Imp and Pmpp are stated in the module datasheet. In real operation the values are almost always worse (the module gets hotter than 25 °C). For realistic values there is NOCT.

See also: NOCT, Voc, Power in Wp / kWp

Voc Temperature Coefficient (β)

How much %/°C Voc changes with temperature. Typically -0.27 to -0.35 %/°C.

Detail

The temperature coefficient β states how much the Voc drops per degree of temperature rise (negative, because voltage falls as it gets warmer). Conversely, at -10 °C the Voc rises by about 10-12 %. This value is the basis of the cold correction in MPPT sizing.

See also: Voc, STC

Bypass diode

Diode in module junction box that bypasses shaded cells. Prevents hot spots.

Detail

Under partial shading the current would be limited by the weakest cell. Bypass diodes (typically 3 per module) route the current around the shaded sub-strings and prevent module damage. The price: the shaded module then only delivers 2/3 or 1/3 of its power.

See also: Mismatch loss, Shading

Glass-glass vs. glass-foil

Glass-glass modules have glass on both sides (often bifacial), glass-foil have polymer backsheet.

Detail

Glass-glass modules last longer (often 30 years warranty), are heavier (about 25-28 kg vs. 20-22 kg) and are usually bifacial (they also use light reflected onto the rear side). Glass-foil is cheaper and lighter, but has a shorter service life (25 years). Relevant for the structural analysis and the mounting system.

See also: Module frame thickness

Module frame thickness

Height of the aluminum frame, typically 30-40 mm. Affects mid/end clamp selection.

Detail

The frame thickness matters for choosing end and mid clamps, which have to grip exactly this height. Glass-glass modules are often frameless (0 mm) — then special clamps or bonded systems are required.

See also: Glass-glass

MPPT & charge controllers(4)

MPP — Maximum Power Point

Point on the I-V curve where module output is maximum.

Detail

On the current-voltage curve (I-V diagram) there is exactly one point at which current × voltage becomes maximum. This MPP shifts with irradiance and temperature. The MPPT tracker adjusts the load so that this point is always held.

See also: MPPT tracker, Vmpp, Imp

MPPT tracker

Electronic controller in charge controller or inverter that finds and holds the MPP.

Detail

MPPT (maximum power point tracker) is an electronic circuit that continuously searches for the optimum operating point. Modern MPPTs often have 2-4 independent trackers, so that shaded string groups or groups with different orientations can be optimised separately.

See also: MPP, String

To MPPT calculator →

MPPT voltage window

Range (vmppMin to vmppMax) within which the tracker can hold the MPP.

Detail

Outside this window the MPPT cannot work. If the voltage is too low it switches off; if it is too high the charge controller is damaged. Rule of thumb: the sum of the module Vmpp must stay inside the window at every temperature (summer as well as winter).

See also: MPP, Voc

MPPT startup voltage

Voltage required for the MPPT to start operation in the morning.

Detail

At low irradiance in the early morning a minimum Voc has to be reached before the MPPT switches on (for example 8 V above battery voltage on the Victron SmartSolar). Important in winter and in weak light.

See also: Voc, MPPT voltage window

String design(6)

String

Modules connected in series feeding a single MPPT input.

Detail

A string is the basic electrical unit: several modules connected in series. The voltages add up, the current stays the same. Several strings in parallel have the same voltage but a higher current. Important: all modules in one string must have the same orientation and be free of shading.

See also: Series connection, Parallel connection, 4S2P notation

Series connection

Modules in series — voltages add, current stays the same.

Detail

With N modules in series: V_string = N × V_module, I_string = I_module. Commonly used to bring the voltage into the MPPT range (e.g. 8 modules at 40 Vmpp = 320 V for a 100/30 charge controller).

See also: Parallel connection, 4S2P notation

Parallel connection

Strings in parallel — currents add, voltage stays the same.

Detail

With N parallel strings: I_total = N × I_string, V_total = V_string. Used when the current limit of the MPPT is not yet reached. Important: all parallel strings must be electrically identical (same number of modules, same orientation).

See also: Series connection, 4S2P notation

4S2P notation

4 modules in series, 2 strings in parallel = 8 modules total.

Detail

Industry standard notation for describing strings. 'S' = series, 'P' = parallel. 4S2P means: 2 strings of 4 modules each, connected in parallel. Voc = 4 × Voc_module, Isc = 2 × Isc_module.

See also: Series connection, Parallel connection

Mismatch loss

Power loss when modules have unequal values or unequal shading.

Detail

Because the string current is limited by the weakest module, every inequality causes a loss. Typical mismatch losses: 1-3 % with identical modules, up to 30 % with heavy partial shading (a single shaded module is enough). Bypass diodes soften the effect.

See also: Bypass diode, Shading

Shading

Shadow on modules — even small shading of one cell drastically reduces string output.

Detail

A single shaded cell can pull the current of the whole string down to the level of that cell. Bypass diodes limit the damage, but 1/3 or 2/3 of the module drops out. Remedy: separate MPPT trackers for shaded areas, or module optimisers.

See also: Bypass diode, Mismatch loss, MPPT tracker

Inverters(7)

Inverter

Device that converts DC from modules to AC (230 V).

Detail

The inverter is the central device of a grid-connected PV system. Variants: string inverter (one or more strings), hybrid inverter (with battery connection), off-grid inverter. Efficiency today is typically 96-98 %.

See also: Hybrid inverter, Off-grid operation

Hybrid inverter

Inverter with integrated battery connection. Combines PV and storage in one device.

Detail

Hybrid inverters (e.g. Fronius GEN24 Plus, Solis Hybrid, Huawei SUN2000) have both PV inputs and a battery connection. Advantage: one device instead of two, simpler wiring. The backup-power function is often optional. Alternative: an AC-coupled solution with Victron MultiPlus and storage.

See also: Inverter, Capacity in kWh

Off-grid operation

System without grid connection, fully self-supplied by PV and battery.

Detail

Off-grid systems need generous sizing (more than 3× the daily consumption as battery reserve), reliable components and usually a backup generator. Typical applications: mountain huts, boats, motorhomes. Victron Quattro and MultiPlus-II are the industry standard here.

See also: ESS, Capacity in kWh

ESS — Energy Storage System

Victron term for grid-parallel storage system with MultiPlus and battery.

Detail

Victron ESS is a software configuration of the MultiPlus/Quattro line that allows grid-parallel operation with battery buffering. The system maximises self-consumption, can switch to backup-power mode during a grid failure and is controlled via Cerbo GX or Venus OS.

See also: Capacity in kWh, Hybrid inverter, Off-grid operation

Victron SmartSolar RS

High-voltage MPPT family (450 V input) for large PV strings.

Detail

The RS series (450/100 and 450/200) allows large string voltages up to 450 V Voc to be wired directly. Important: the RS 450/100 has 2 MPPT trackers, the RS 450/200 has 4. The classic SmartSolar units (100/30, 150/35, 250/100) are single-tracker devices for smaller systems.

See also: MPPT tracker, ESS

MultiPlus / Quattro

Victron inverter-charger family for ESS and off-grid.

Detail

MultiPlus and MultiPlus-II are the standard inverter/chargers of the Victron range for grid-parallel and off-grid applications. The Quattro additionally has a second AC input (e.g. for a generator) with uninterrupted transfer. EasySolar-II combines MultiPlus, SmartSolar and distribution in a single enclosure.

See also: ESS, Off-grid operation

Phoenix Inverter

Pure inverter (no charger, no grid) for converting battery DC to AC.

Detail

Phoenix Smart and Phoenix VE.Direct are pure inverters without a charging function. They are used when only DC energy (battery) has to be converted to AC, without grid-parallel operation. Typical in motorhomes or as a pure backup-power inverter.

See also: Off-grid operation

Battery storage(5)

Capacity in kWh

Maximum storable energy. For lithium often quoted as 'usable' (80-90% of gross).

Detail

Capacity is stated in kWh, often distinguishing between 'gross' (chemically available) and 'usable' (limited by DoD). With LiFePO4 90-95 % is usable, with lead only about 50 %. Sizing rule of thumb: 1-1.5 kWh of storage per 1 kWp of array.

See also: DoD, C-rate

DoD — Depth of Discharge

How deep a battery can be safely discharged (% of capacity).

Detail

The DoD determines the usable capacity. LiFePO4: 90-95 % DoD is safely possible. Lead-acid: typically 50 % DoD, so as not to halve the service life. AGM/gel: 50-60 %. The number of charge/discharge cycles depends strongly on the DoD.

See also: Capacity in kWh, LiFePO4

C-rate

Charge/discharge current relative to capacity. 1C = full capacity in 1 hour.

Detail

With a 10 kWh battery, 0.5C means 5 kW of charge/discharge power. LiFePO4 typically tolerates 0.5-1C without loss of service life, lead only 0.1-0.2C. Important for inverter sizing: its charging power must not exceed the C-rate.

See also: Capacity in kWh

LiFePO4 — Lithium Iron Phosphate

State of the art for home storage. Safe, long-lived (>6000 cycles), non-flammable.

Detail

LFP (or LiFePO4) is the chemistry of most modern home storage systems (Pylontech, BYD, Victron Smart Lithium, Fronius Solar Battery). Advantages over NMC: higher thermal stability, longer service life, no cobalt. Disadvantage: lower energy density (more space for the same kWh).

See also: Lead-acid / AGM / Gel, Capacity in kWh, DoD

Lead-acid / AGM / Gel

Old storage technology. Cheap upfront, short lifespan (5-7 years).

Detail

Despite being technically inferior to lithium, lead is still common in off-grid systems. AGM (absorbent glass mat) and gel are the maintenance-free variants. Maximum DoD: 50 %, otherwise the cycle life is halved. Efficiency: 80-85 % (LiFePO4: 95 %+).

See also: LiFePO4, DoD

Cables & wiring(5)

Cable cross-section

Conductor cross-section area in mm². Determines current capacity.

Detail

Stated in mm² (copper or aluminium cross-section). In PV systems typically 4 mm² or 6 mm² for PV strings and 25-95 mm² for battery-to-inverter connections. Selection criteria: current carrying capacity (DIN VDE 0298-4), voltage drop (max. 1-3 %) and fuse sizing.

See also: Voltage drop, Current carrying capacity

To cable calculator →

Voltage drop

Voltage lost in the cable due to resistance. Max 1% on PV strings.

Detail

Calculated as ΔU = 2 × I × L × ρ / A (for DC), for AC additionally with cos φ. On PV strings 1 % is the industry standard (more wastes energy); on 230 V AC 3 % is permitted (DIN VDE 0100-520). The voltage drop rises with current and length and falls with cross-section.

See also: Cable cross-section

Current carrying capacity

Maximum continuous current a cable can carry without overheating.

Detail

The current carrying capacity depends on the material (Cu vs. Al), the cross-section, the installation method (free air, buried, in walls) and the ambient temperature. Tables can be found in DIN VDE 0298-4. On PV strings the Iz is additionally multiplied by 1.25 as a reserve for high irradiance.

See also: Cable cross-section, Installation method

Installation method

How a cable is laid (free, conduit, buried) — determines allowed current.

Detail

Standardised installation methods according to DIN VDE 0298-4: A1 (in a thermally insulated wall), B2 (in conduit in a wall), C (on a wall), E (free in air). The current carrying capacity can differ by a factor of 1.5-2 between A1 and E, which makes it important for sizing.

See also: Current carrying capacity

Solar cable (H1Z2Z2-K)

Special UV- and temperature-resistant cable for PV outdoor wiring. Standard: EN 50618.

Detail

Solar cables are double-insulated, UV-resistant, halogen-free, temperature-resistant up to 120 °C and approved for 1500 V DC. Designation H1Z2Z2-K (formerly PV1-F). Standard cross-sections: 4 mm² and 6 mm². Never use ordinary NYY-J cable for DC runs.

See also: Cable cross-section

Roof & structure(7)

Eaves

Lower edge of the roof (drip edge). Where rainwater runs off, usually with gutter.

Detail

The eaves are the lower horizontal edge of the roof. In the PV planner the 'eaves clearance' is the mandatory distance (typically 300 mm) between the lower edge of the module field and the roof edge, so that snow load does not press into the gutter.

See also: Ridge, Verge / Gable, Rafter

Ridge

Upper edge of the roof where two sides meet. Ridge height = highest roof point.

Detail

On a gable roof the ridge runs lengthways in the middle between the two roof surfaces. In the PV planner the 'ridge clearance' is the mandatory distance (typically 300 mm) between the upper edge of the module field and the ridge, so that the ridge tile stays accessible.

See also: Eaves, Verge / Gable

Verge / Gable

Side edge of the roof (gable side).

Detail

The verge is the lateral edge of the roof towards the gable. In the PV planner the 'verge clearance' (typically 300 mm) is used as a safety distance between the side edge of the module field and the side edge of the roof.

See also: Eaves, Ridge

Rafter

Load-bearing timber of a sloped roof, runs vertically from eaves to ridge.

Detail

Rafters are the structurally load-bearing timber beams (usually 8/16 cm or 10/20 cm). Typical rafter spacing is 70-90 cm. Important for fixing the mounting system: roof hooks and double hooks must be screwed INTO the rafter, not into the battens. Hence the rafter snap logic in the mounting-system view.

See also: Purlin, Roof battens

Purlin

Horizontal load-bearing beam of a purlin roof, perpendicular to rafters.

Detail

Purlins (eaves purlin at the bottom, middle purlin or ridge purlin at the top) carry the rafters in purlin roofs. On trapezoidal sheet and sandwich-panel roofs, hanger bolts are set directly into the purlin.

See also: Rafter

Roof battens

Thin battens on which tiles sit. NOT load-bearing for hooks!

Detail

The roof batten (about 30/50 mm) lies crossways on the rafters and carries the tiles. Important: PV fasteners must never sit in the battens alone — they always have to reach the rafter. Roof hooks often have a shaped geometry that clears the tile profile AND reaches the rafter.

See also: Rafter

Roof covering

Outer roof skin: clay/concrete tiles, beaver tail, slate, trapezoidal sheet, standing seam, corrugated fiber cement.

Detail

The roof covering determines the fixing logic of the mounting system: tiles → roof hook (with or without a recess for the tile profile), plain (beaver-tail) tiles → double hook, trapezoidal sheet → hanger bolt with sealing washer, standing seam → seam clamp (clamps without drilling), corrugated fibre cement → hanger bolt through the crest of the corrugation.

See also: Mounting hook, Hanger bolt

Mounting structure(9)

Mounting hook

Steel hook screwed into the rafter, protruding under the covering.

Detail

The standard fixing for tiled and slate roofs. The hook is screwed onto the rafter (with two or three 6×80 or 8×80 screws); the tile is partly notched, or special hook shapes clear the tile profile. The rail is then clamped onto the top of the hook.

See also: Double mounting hook, Hanger bolt, Rafter

Double mounting hook

Larger hook with two contact points on the rafter. For higher loads or critical structure.

Detail

The double hook is used for higher pull-out loads (wind suction) or with two-layer systems. It spreads the load over two screw points and can take two or more screws per fixing. In the plan it appears as a plate with two black dots (versus a single dot for the normal roof hook).

See also: Mounting hook, Rafter

Hanger bolt

Wood screw with metric thread — wood side into rafter, metric side gets the rail nut.

Detail

Hanger bolts are the standard fixing for trapezoidal sheet, corrugated fibre cement and sandwich-panel roofs (M8 or M10, lengths 150-300 mm). One end is a wood thread (into the rafter or purlin), the other a metric thread with an EPDM sealing washer and a nut to take the rail. On trapezoidal sheet it always sits on the crest, never in the trough.

See also: Mounting hook, Roof covering

C47 rail

Standard mounting rail 47×40 mm aluminum, available in 3.6 m or 5.9 m lengths.

Detail

C47 is the most widely used PV rail in the German-speaking region (Solarplanit, K2, IBC). Cross-section: 47 mm wide, 40 mm high, with a T-slot for the clamps. Stock lengths: 3,600 mm and 5,900 mm. For longer rail runs, several pieces are coupled together with rail splices.

See also: Rail splice / connector, Module clamp

Rail splice / connector

Metal coupler joining two C47 rails end to end.

Detail

Required when the total rail length exceeds the 5.9 m stock length. The splice is pushed into the inner section of both rails and clamped tight. Shown in the plan as a yellow symbol at the joint. Important: joints should if possible not lie in the area of a clamp.

See also: C47 rail

Module clamp (end / mid)

Aluminum clamp that presses the module frame onto the rail.

Detail

End clamps sit at the edge of a module row (one side presses the module, the other side ends free). Mid clamps sit between two modules and hold both at once. Clamps must match the module frame thickness exactly (30, 35, 40 mm), otherwise there is no secure hold. Typical tightening torque: 10-15 Nm.

See also: C47 rail

Cross connector

Connector joining two rails crosswise (e.g. in 2-layer UK with horizontal bearer + vertical module rails).

Detail

In a two-layer mounting system (DP_2L) there is a continuous lower bearer rail and upper module rails that cross it at right angles. A cross connector sits at every crossing point. This configuration carries more load than a single-layer system, but is more expensive and heavier.

See also: C47 rail

Ballast (flat roof)

Weight (typically concrete slabs) holding flat-roof structure against wind suction.

Detail

On flat-roof systems the mounting structure is not drilled through the roof but weighted with ballast against wind suction. Calculated according to ÖNORM B 1991-1-4 / EN 1991-1-4. Typically 100-300 kg per module, depending on wind zone, building height and module tilt. The calculation takes into account the friction coefficient between the roof membrane and the structure.

See also: Elevation system

Elevation system (flat roof)

Flat-roof UK that tilts modules 10-15° toward south or east/west.

Detail

On flat roofs the modules are not laid flat (too little yield) but elevated at 10-15°. Variants: south elevation (highest yield per module) or east/west elevation (more modules on the same area, a more even daily curve). Standard products: K2 D-Dome, IBC TopFix 200.

See also: Ballast

Structural loads(4)

Snow load

Vertical load from snow on the roof. Depends on snow zone, elevation, roof pitch.

Detail

Calculated according to ÖNORM B 1991-1-3 or DIN EN 1991-1-3. Snow load zones 1-4 in Austria, plus special values for high alpine areas. A typical base load of 0.75 kN/m² is modified by an altitude factor and a shape coefficient (roof pitch). PV modules must carry the full snow load without deformation — hence the structural calculation in the planner.

See also: Wind load, ÖNORM B 1991-1-3

Wind load

Pressure or suction from wind. On flat roofs suction dominates and can tear modules off.

Detail

Calculated according to ÖNORM B 1991-1-4. Key inputs: wind zone (1-4), building height, terrain category (urban vs. rural) and roof shape. At the roof edges (corner and edge zones) the suction can be 2-3 times higher than in the middle — additional fasteners are then required there.

See also: Snow load, ÖNORM B 1991-1-4

Pull-out load

Maximum tensile force per fastener pulling it out of the rafter (wind suction).

Detail

For every roof-hook fixing point the calculated pull-out load (kN) must stay below the permissible load of the wood screw. Rule of thumb: an 8×80 screw in spruce holds about 2.5-3 kN of pull-out force. For higher loads: double hooks or thicker screws.

See also: Wind load, Rafter

Utilization

What % of allowable load the chosen system actually uses. Below 100% = OK.

Detail

In the structural result: a utilisation of 24 % means the system uses only a quarter of its load capacity (plenty of reserve). 95 % would be critical (close to the limit); over 100 % means calculated failure — then more fasteners or stronger components are needed.

See also: Pull-out load

Yield & economics(4)

Specific yield (kWh/kWp)

Annual yield per installed kWp. Central Europe typical 900-1100 kWh/kWp.

Detail

The specific yield allows systems to be compared independently of their size. Influencing factors: location (southern Germany 1000-1100, northern Germany 850-950), orientation (south 100 %, east/west 85-90 %), tilt (20-35° optimal), shading, module quality and inverter efficiency.

See also: Self-consumption rate

Self-consumption rate

What % of PV power is consumed directly in the building (instead of fed in).

Detail

Without storage typically 25-35 %, with a 10 kWh battery 60-80 %, with a heat pump, an electric car and storage up to 90 %. A higher self-consumption rate means better economics, because electricity used on site (about 25-30 ct/kWh) is worth more than electricity fed in (5-12 ct/kWh in Austria in 2025).

See also: Self-sufficiency

Self-sufficiency

What % of household energy demand is covered by PV (rest from grid).

Detail

While self-consumption says how much of the PV electricity is used, self-sufficiency describes the share of the household demand that comes from PV. With 10 kWp plus a 10 kWh battery, 60-75 % self-sufficiency is typical. 100 % would mean off-grid operation (realistically not achievable in winter without a huge battery).

See also: Self-consumption rate

Feed-in tariff

Compensation for surplus PV power fed into the grid (in AT via OeMAG).

Detail

In Austria, OeMAG pays a subsidised tariff for 13 years (between 5.5 and 12 ct/kWh in 2024/25, depending on the investment grant received). The alternative is free market participation via an electricity trader (often slightly more, but variable). Important: high self-consumption is usually more economical than high feed-in.

See also: Self-consumption rate

Standards & codes(6)

ÖNORM B 1991-1-3 (snow loads)

Austrian standard for snow load characteristic values.

Detail

Defines snow load zones 1-4 in Austria, the altitude adjustments from 200 m above sea level and the shape coefficients for each roof pitch. German counterpart: DIN EN 1991-1-3 with the national annex. Eurocode basis: EN 1991-1-3.

See also: Snow load

ÖNORM B 1991-1-4 (wind loads)

Austrian standard for wind pressure and suction on buildings.

Detail

Defines wind zones 1-4 in Austria (map), the height categories, the pressure coefficients for each area of a component (corner, edge, middle) and the friction coefficients. German counterpart: DIN EN 1991-1-4.

See also: Wind load

OVE E 8101

Erection of electrical installations in AT — basis for cable sizing in the tool.

Detail

OVE E 8101 is the Austrian erection standard for low-voltage installations. The cable calculator uses the current carrying capacity tables from this standard.

See also: Cable cross-section

DIN VDE 0298-4

German standard for current capacity by installation method.

Detail

Defines, for every installation method (A1, B2, C, E, D) and every cross-section, the maximum continuous current carrying capacity. It is the basis of the capacity column in the cable calculator.

See also: Current carrying capacity

DIN VDE 0100-712

Special provisions for PV systems in Germany.

Detail

Erection of PV power supply systems: requirements for DC wiring, protective measures, PV fuses and isolating devices. The corresponding international base standard is IEC 60364-7-712.

See also: Solar cable

EN 50618 (solar cable standard)

European standard for PV solar cables (designation H1Z2Z2-K).

Detail

Defines the requirements for PV special cables: 1500 V DC, double insulation, UV resistance, halogen-free, temperature range -40 to +120 °C, service life 25 years at 90 °C. All PV string wiring should comply with this standard.

See also: Solar cable

Related tools

Read on

PV Glossary: Voc, MPP, Wp, C47 | green-future.at